Cable sizingLV

Cable calculations: section versus cumulative voltage drop

When a reviewer asks where a voltage drop is measured from, the circuit reference alone may not tell the whole story. Record the start and end points alongside the result.

Applies toLow-voltage AC cable worksheet

1. Two voltage drops, two purposes

Section voltage drop describes the cable run between two identified points. Cumulative voltage drop also takes the upstream path into account. The cable worksheet checks a single run against the limit entered by the engineer.

Software test case · Single-phase 200 V, 100 A, 100 m one-way, 3% limit
CandidateReference ratingSection drop
Calculating example…

2. What the calculation should show

Keep the route, one-way length, load basis, power factor and impedance source with the selected section. In the software test shown above, both candidates meet the design current. Voltage drop determines the selection.

Try the cable sizing worksheet

Compare candidates with your own circuit data.

Open tool

3. When upstream data is incomplete

Identify the missing upstream section in the review notes. Report the available value as a section result and leave the cumulative check open until the upstream design is available.