Cable calculations: section versus cumulative voltage drop
When a reviewer asks where a voltage drop is measured from, the circuit reference alone may not tell the whole story. Record the start and end points alongside the result.
1. Two voltage drops, two purposes
Section voltage drop describes the cable run between two identified points. Cumulative voltage drop also takes the upstream path into account. The cable worksheet checks a single run against the limit entered by the engineer.
| Candidate | Reference rating | Section drop |
|---|---|---|
| Calculating example… | ||
2. What the calculation should show
Keep the route, one-way length, load basis, power factor and impedance source with the selected section. In the software test shown above, both candidates meet the design current. Voltage drop determines the selection.
3. When upstream data is incomplete
Identify the missing upstream section in the review notes. Report the available value as a section result and leave the cumulative check open until the upstream design is available.